Features Fire Alarm Control Panel HC-5AL, Zona 5 :
Alarm Verification: To avoid false alarm from environment interference and unstable pulse. On receiving a fire signal from detector or manual call point, Panel accumulates the fire signal before Alarm Verification time: 12 seconds, if the fire signal is still existing, Panel start to alert.
Zone test: Alarm and Fault function test.
Back up battery test.
Fault indications for wire disconnection, unstable AC power, battery short circuit or disconnection and fuse trouble.
Different sounds to indicate fire alarm or disconnection.
Annunciator is available to connect with.
Spesification Fire Alarm Control Panel HC-5AL:
Model : HC-5AL
Total Loops : 5 Loops
Input Power : 220VAC 50/60Hz
Aux. Power (Spare Battery) : DC 24V 300mAH (NI-Cd Battery)
Charging Voltage/Current : DC 29V 60mA
Loop Voltage, Current : Nomal: DC24V, Short-Circuit: 5V, Under 30mA
Exterio Resistance : Round-trip under50Ω
Amount of Smoke Detectors : Max.
Amount of Connection: 20/ Loop Amount of Heat Detectors : No Limit (Except Electronic Type)
End of Line Resistance : 10KΩ
Output Current for Indicating Lamp : Max.
Output Current: 120mA Output Current for Alam Bell : Max. Output Current: 120mA
Case Material : ABS resin with non-flammability
Auxiliary Contact : 1 Null-Valtage Contact (N/O, 250VAC, 7A)
===================
Untuk Info dan Pemesanan Hubungi :
DARMATEK
Contact: Subarkah
Telpon : 021-71031268
H P : 081283804273/085774067221
WA : 081932632003
Email : subarkah18@yahoo.co.id
Gmail : darmatek1@gmail.com
Pin BB : D2A771BD
Link : http://darmatek.indonetwork.co.id
http://darmatek01.blogspot.com
http://sirineindo.blogspot.com
http://tokomoisturemeter.blogspot.com
Web : http://www.darmatek.net
Tidak ada komentar:
Posting Komentar